EATON/Cutler Hammer FP-5000-00 Feeder Protection Relay

by Eaton / Cutler Hammer

Contact for Quote: 800-909-3660 | sales@naswgr.com

FP-5000


Cutler Hammer FP-5000-00 Feeder Protection Relay
Power Supply: 48-125vDC, 100-120vAC 20VA
CT: 5 Amp Nominal
VT: 69/120vAC Nominal 
Inner/Outer Chasis Style #: 66D2041G01
Inner Chasis FP5000-00-IC Style #: 66D2038G01
Outer Chasis FP5000-OC Style#: 66D2039G01

Protection Features • Phase overcurrent A. 2-stage instantaneous with timers (50P-1 & 50P-2) B. Inverse time overcurrent (51P) C. Voltage restraint inverse time overcurrent (51P2) D. 10 standard curves E. Reset 1. Instantaneous 2. Time Delay 3. Calculated • Independent measured ground or neutral overcurrent element A. 2-stage instantaneous with timers (50X-1 & 50X-2) B. Inverse time overcurrent (51X) C. 10 standard & 3 user defined custom curves D. Reset 1. Instantaneous 2. Time Delay 3. Calculated • Independent calculated ground or neutral overcurrent element A. 2-stage instantaneous with timers (50R-1 & 50R-2) B. Inverse time overcurrent (51R) C. 10 standard curves D. Reset 1. Instantaneous 2. Time Delay 3. Calculated • Breaker failure (50BF) • Phase current unbalance and sequence protection (46) • Phase voltage unbalance and sequence protection (47) • Main 3-phase under/overvoltage (27M1/59M1) • Power Protection (32) • Under/over frequency (81U/81O) • Auxiliary single-phase under/overvoltage (27A1/59A1) • Neutral voltage (59N1) • Power factor (55) • Zone interlocking for bus protection (87B) • Additional elements for alarming on: A. Instantaneous overcurrent (50P-3, 50X-3, 50R-3) B. Under/overvoltage (27M-2/59M-2, 27A-2/59A-2) C. Power (32) D. Under/over frequency (81U-2, 810-2) E. Current unbalance (46-2) F. Voltage unbalance (47-2) G. Neutral voltage (59N-2)

Metering Features • Amps & amps demand • Volts • Volt-amps • Watts & kW demand • kwh, net kwh • Vars & kvar demand • Kvarh & net kvarh • Power factor • Frequency • Min/max recording • Trending (load profile over time) • Current & voltage THD

Monitoring Features • Trip coil • Breaker wear (accumulated interrupted current) • Oscillography (256 cycles total, up to 16 events) • Trip data logs (up to 16 events) • Sequence of events report (up to 100 events) • Clock (1 ms time stamping)

Control Functions • Remote open/close • Local open/close • Programmable I/O • Programmable logic gates and timers • Multiple setting groups (up to 4) • Sync-Check (25) • Cold load pickup

Mechanical Features • Full drawout unit (automatic CT shorts) • Standard IQ Panel Cutout retrofit possible • Outline Size is approximately 6.5" (165.1 mm) wide 10" (254 mm) high 7" (177.8 mm) deep • Weight for outer case is 5.0 lbs. (2.27kg), inner drawout 5.8 lbs.(2.63 kg) Approximate shipping weight is 16.5 lbs. (7.48 kg)

Design Features • Password protected • Data acquisition with necessary resolution and sampling frequency A. 3-phase currents B. Ground current C. 3-phase voltages D. Auxiliary voltage E. rms values (current and voltages) F. Power [real (W), reactive (VAR), apparent (VA)] G. Power factor (apparent and displacement) H. Fequency I. Power and current demand J. Min/max values K. Energy  Control power A. ac or dc control power (100–120 Vac, 50/60 Hz or 48–125 Vdc) B. ac or dc control power (100–250 Vdc or 100-240 ac, 50/60 Hz) C. Consult factory for availability of other voltage power supplies. • Nonvolatile memory for Settings, Waveforms, Sequence of Event Logs, Trip Logs and Trending • Determine condition of acquired data relative to settings A. Current, voltage, and frequency protection • Monitoring and reporting of additional system information A. Oscillography B. Sequence of events recording C. Trip target data D. Real-time clock E. Breaker wear, trip coil F. Signal harmonic content • Zone interlocking • User access to processed data (through PowerNet and PowerPort) • Meets ANSI, IEC, UL, and CUL standards

Communication Features • Local HMI • Addressable • Local communication port (RS-232 on 9-pin DIN) • Remote communication ports A. INCOM FSK • Protocols A. INCOM/IMPACC Communications Standard, IL 17384 - Part A, Version 3.0 B. MODBUS RTU

Self-Test Features • Hardware A. Processor integrity B. RAM C. PROM checksum D. Analog input circuitry • Application A. Comparison of current flow with apparent state of breaker B. Comparison of apparent and set phase sequence C. Determination of correct voltage or current phasor relationships and/or balance D. Setting integrity

Each FP-5000 Relay is Cleaned, Tested with Report and Caries our One Year Warranty.

Standard lead time (1-3) days prior to shipping. If item is needed sooner please call or email.

Call 800-909-3660 or email sales@naswgr.com with questions.

After hours emergency hotline 216-402-0507 or 216-570-2725

NASPG38003 , NASPG38004 , NASPG38005 , NASPG38006 , NASPG38007 , NASPG38008 , NASPG41980 , NASPG41981 , NASPG41982 , NASPG41983 , NASPG41984 , NASPG41985 , NASPG41986 , NASPG41987 , NASPG41989 , NASPG41990 , NASPG41992 , NASPG41993 , NASPG41994 , NASPG41995 , NASPG41996 , NASPG41997 , NASPG41998 , NASPG41999 , NASPG42000 , NASPG42001 , NASPG42003 , NASPG42004 , NASPG42006 , NASPG42007 
Location: 6012A

*Missing Outer Chasis*
NASPG41988 , NASPG41991 , NASPG42002  Location: 6012A


North American Switchgear, Inc. is an industry leader in the sale of new, used and out-of-production industrial circuit breakers, switchgear and associated parts.  Our Cleveland, OH facility spans over 300,000 square feet and houses over 13,000 low and medium voltage circuit breakers from all major manufacturers.  Aside from the sale of circuit breakers, switchgear and replacement parts, NAS also offers equipment recondition and repair services.  For more information please visit our website at www.naswgr.com, call 800-909-3660 or email sales@naswgr.com 

 

 Visit our website www.naswgr.com